40 CFR Part 84 Subpart C
Techs log the service once. The shop keeps the leak rate, the repair case, and the file an inspector can read.
Open the demoFor penalties assessed on or after January 8, 2025, 40 CFR 19.4 Table 1 sets the Clean Air Act maximum at $124,426 per day for each violation under 42 U.S.C. 7413(b) (90 FR 1375). That figure is a maximum. This tool does not calculate a fine.
One button for a 12 to 36 month narrative, and an audit pack for the date range you choose.
Each covered appliance is green, yellow, or red from its leak rate and open repair case.
A calendar-year loss of at least 125 percent of the full charge is flagged on appliances of 15 lb or more.
In-app notices, and email when it is configured, for threshold, repair, verification, and inspection dates.
Chronic-leaker and extension requests export field by field for the shop's own file.
Revisions are kept with the record. Appliance files stay until three years after retirement.
Assigned appliances and cylinders stay on the phone. Entries sync when the signal returns.
Covered means the shop can keep that record here. Coming soon means this version does not.
40 CFR 84.106(l)
Stored on the appliance, with a revision each time the charge changes.
40 CFR 84.106(l)(2)
Date, part, service type, person, pounds, refrigerant, and full charge when it applies.
40 CFR 84.102 and 84.106(b)
Annualizing and rolling average are both calculated. The method is stored with the rate.
40 CFR 84.106(d) and (e)
30 days, or 120 days for an industrial-process shutdown. The case stays open until both tests pass.
40 CFR 84.106(g)
The next due date is stored after a successful follow-up test.
40 CFR 84.106(m)
A field-by-field worksheet for the shop file. It is not an upload file for EPA's system.
40 CFR 84.106(f)
A field-by-field worksheet from the open leak case.
40 CFR 84.106(l)
Appliance records stay until three years after retirement. Other records stay three years. The date is calculated. Nothing is deleted on a schedule.
40 CFR 84.108
Install date, last calibration, and alerts are recorded. A continuous sensor log is not in this version.
40 CFR 84.106
A service line can be marked purged or destroyed, and a PDF or image of the destruction record can be kept with it.
40 CFR 84.106(m)
The workbook cell layout is not filled in here.
State rule
Not in this version.
Annualizing uses the current addition over the days since the previous addition. Rolling average sums additions inside 365 days, or since the last successful follow-up if that is later. Thresholds are 10 percent, 20 percent, and 30 percent by appliance category. Both results are shown on the unit history.
Comfort cooling, refrigerated transport, and other appliances
Commercial refrigeration
Industrial process refrigeration
Section citations were checked against the eCFR text dated October 20, 2026. The penalty amount was taken from the January 8, 2025 rule that amends 40 CFR 19.4 Table 1 (90 FR 1375). No later EPA inflation adjustment was found in the Federal Register through October 22, 2026. This page describes what the product records. It does not decide whether a particular appliance is in compliance.
Part 84 Subpart C recordkeeping and leak repair apply to appliances with a full charge of 15 pounds or more that contain a regulated substance or a substitute with a GWP above 53, other than appliances that contain only ozone-depleting substances and other than residential and light commercial air conditioning and heat pumps. That applicability begins January 1, 2026 (40 CFR 84.106(a)). Ozone-depleting appliances of 50 pounds or more follow 40 CFR 82.157.
The facility uses either the annualizing method or the rolling-average method defined in 40 CFR 84.102. The first calculation after January 1, 2026 uses the substitutions in 40 CFR 84.106(b). Regulatory thresholds are 20 percent for commercial refrigeration, 30 percent for industrial process refrigeration, and 10 percent for comfort cooling, refrigerated transport, and other appliances (40 CFR 84.106(c)(2) and 40 CFR 82.157(c)(2)). A shop alert can only be stricter than those numbers.
When the rate exceeds the regulatory threshold, the repair is due in 30 days, or 120 days when an industrial process appliance is mothballed for a shutdown (40 CFR 84.106(d) and 40 CFR 82.157(d)). The case stays open until both an initial verification test and a follow-up verification test pass (40 CFR 84.106(e)). After that follow-up, commercial refrigeration and industrial process refrigeration appliances of 500 pounds or more are due for inspection quarterly; other covered appliances are due annually (40 CFR 84.106(g)).
A calendar-year loss of at least 125 percent of the full charge is a chronic leaker (40 CFR 84.106(j); 40 CFR 82.157(j) uses the same percent at 50 pounds). Commercial refrigeration and industrial process refrigeration appliances of 1,500 pounds or more that are subject to Part 84 need an automatic leak detection system (40 CFR 84.108). Starting January 1, 2029, supermarket systems, refrigerated transport, and automatic commercial ice makers are flagged when virgin refrigerant is added (40 CFR 84.112(e)). Starting January 1, 2028, an empty disposable cylinder is flagged for heel removal (40 CFR 84.116(a)). Evacuation practice is governed by 40 CFR 82.156. Safe disposal of appliances is 40 CFR 82.155. Technician cards follow 40 CFR 82.161.